FyreLine Resettable LHD Cable, Stainless Steel Braided, 54°C to 100°C, 500m
VdS Model Number FyreLine Resettable LHD Cable, Stainless Steel Braided, 54°C to 100°C
UL Model Number –
Construction Overall insulated, 4-core twisted with 100% coverage foil-shield and shield dump wire
Final Insulation Stainless Steel Braid (min. 70% coverage)
Wire Overall Diameter 5.33mm (0.210in)
Weight 39.3kg/km
Colour Silver
Minimum Bend Radius 75mm (3in)
Maximum Ambient Temperature Dependent upon Alarm Temperature
Minimum Ambient Temperature -40°C
Maximum Recoverable Temperature +125°C
Continuous Operating Humidity Range Ambient temperatures between -40°C to +40°C : 0% to 99% RH ambient temperatures greater than +40°C) : 0% to 75% RH
Minimum Zone Length Class A1I/A2I and 54°C alarm settings : 50m / 164ft all other alarm settings: 30m / 100ft
Maximum Zone Length 500m / 1640ft
EN54-22 Environmental Group II
White Core Resistance Per Metre Approx 17 Ω/m
Red Core Resistance Per Metre Approx 3.3 Ω/m
Clear Core Resistance Per Metre (each) Approx 0.1 Ω/m
Features Stainless steel braid for increased mechanical toughness and abrasion resistance. Suitable for indoor/outdoor use with limited exposure to direct sunlight and not exposed to harsh chemicals.