FyreLine Resettable LHD Cable, Nylon, 54°C to 100°C, 100m
VdS Model Number FyreLine Resettable LHD Cable, Nylon, 54°C to 100°C
UL Model Number FLR100-NYL, FyreLine Resettable Heat Detection Cable with Nylon Outer Jacket (1)
Construction Overall insulated, 4-core twisted with 100% coverage foil-shield and shield dump wire
Final Insulation Nylon
Wire Overall Diameter 6.00mm (0.235in)
Weight (kg/km) 36.3
Colour Black
Minimum Bend Radius 100mm (4in)
Maximum Ambient Temperature Dependent upon Alarm Temperature
Minimum Ambient Temperature -40°C
Maximum Recoverable Temperature +125°C
Continuous Operating Humidity Range Ambient temperatures between -40°C to +40°C : 0% to 99% RH ambient temperatures greater than +40°C) : 0% to 75% RH
Minimum Zone Length Class A1I/A2I and 54°C alarm settings : 50m / 164ft all other alarm settings: 30m / 100ft
Maximum Zone Length 500m / 1640ft
EN54-22 Environmental Group II
White Core Resistance Per Metre Approx 17 Ω/m
Red Core Resistance Per Metre Approx 3.3 Ω/m
Clear Core Resistance Per Metre (each) Approx 0.1 Ω/m
Features Hard nylon outer jacket. UV stable for indoor and outdoor use in direct sunlight. Excellent resistance to hydrocarbons.